MODEL GXT-6000MTPLUS CX230
CAPACITY 6000 VA / 5400 W
Input
Nominal Voltage 208/220/230/240VAC
Input Voltage Range 110-300 VAC (Based on load at 50%); 176-300 VAC (Based on load at 100%)
Frequency Range 46~54 Hz or 56~64 Hz
Power Factor ≥ 0.99 @ Nominall Voltage (100% load)
OUTPUT
Output Voltage 208/220/230/240VAC
Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤ 3 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)
Transfer Time
Bypass to Inverter (Line mode) Zero
Inverter to Bypass Zero
Waveform (Battery Mode) Pure Signwave
Waveform (Batt. Mode)
AC Mode 92%
Battery Mode 90%
BATTERY
Battery Type 12V/ 9 AH
Numbers 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (max.) 1.0A / 2.0A
Charging Voltage 218.4 VDC±1%
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Dimension, D x W x H (mm) 369×190×688
Net Weight (kg) 61
ENVIRONMENT
Humidity 0-95% RH @ 0-50°C (non-condensing)
Noise Level Less than 55dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC.
Optional SNMP Power management from SNMP manager and web browser